Bearings are core components of industrial equipment. Insufficient lubrication will aggravate friction and induce abnormal vibration, eventually leading to equipment failure. The kurtosis value of bearing vibration signals (a statistical parameter reflecting peak characteristics of signals, which rises significantly in early‑stage faults) can be monitored to quantitatively evaluate lubrication conditions.
‑ Objective 1: The edge‑computing acquisition unit collects vibration data in real time and calculates kurtosis automatically.
‑ Objective 2: The PLC reads kurtosis values and judges whether bearings require lubrication via threshold setting, so as to realize intelligent lubrication management.
Overall hierarchical architecture Perception Layer (Vibration Sensor) → Edge Layer (Edge‑computing Acquisition Unit) → Control Layer (PLC) → Application Layer (HMI / Alarm System)
Layer |
Core Equipment / Functions |
|---|---|
Perception Layer |
Vibration acceleration sensor (mounted on bearing housing to acquire high‑frequency vibration signals; measuring range ±50 g, sampling rate ≥10 kHz). |
Edge Layer |
Edge‑computing acquisition unit (processes vibration signals, calculates kurtosis, and transmits data to PLC via industrial bus). |
Control Layer |
PLC (reads kurtosis values, executes threshold‑judgment logic, and outputs lubrication pump commands or alarm signals). |
Application Layer |
HMI (displays kurtosis value and lubrication status), audible‑visual alarm (triggers reminder upon abnormality), lubrication pump (performs lubrication actions). |
Edge acquisition unit: supports 4‑channel analog vibration‑signal input (connecting vibration sensors), 24‑bit AD conversion. Real‑time computation: supports statistical‑value calculation, integral calculation, FFT analysis, envelope analysis and filtering; supports deployment of Python / C++ algorithms. Industrial communication: compatible with Modbus TCP / Profinet for PLC interconnection.
Kurtosis formula: \(K=\frac{E[(x-\mu)^4]}{{(E[(x-\mu)^2])}^2}\) ‑ x: Sampling value of vibration‑acceleration signal ‑ \(\mu\): Mean value of the signal
Physical meaning: Kurtosis ≈ 3 under normal conditions; kurtosis>5 for insufficient lubrication or early‑stage faults (calibration shall be performed according to bearing models).
‑ Signal acquisition: One group of data is collected approximately every 1 second.
‑ Pre‑processing: DC component removal (mean subtraction) and signal filtering.
‑ Kurtosis calculation: Real‑time calculation per formula; output kurtosis value with 2 decimal places reserved.
‑ Data upload: PLC reads kurtosis values from edge‑computing acquisition unit over Modbus TCP (address to be confirmed).
PLC: supports Modbus TCP communication, equipped with digital output module to control lubrication pump.
// Read kurtosis value (K) from edge acquisition unit
K = MODBUS_READ(edge‑acquisition‑unit‑IP, kurtosis‑address, 1)
// Threshold setting (calibrated against bearing model and operating condition)
K_NORMAL = 3.0 // Threshold for normal status
K_WARN = 4.5 // Warning threshold (lubrication recommended)
K_ALARM = 6.0 // Alarm threshold (lubrication mandatory)
// Logical judgment
IF K < K_NORMAL THEN
Status = "Normal"; Lubrication_pump = OFF; HMI shows Green
ELSIF K >= K_WARN AND K < K_ALARM THEN
Status = "Lubrication required"; Lubrication_pump = ON (hold 30 s); HMI shows Yellow
ELSE
Status = "Urgent lubrication"; Lubrication_pump = ON (hold 60 s) + audible‑visual alarm; HMI shows Red
ENDIF
// Historical‑data storage
Store K value and status into PLC data block DB1 every 5 minutes; trend query supported on HMI.
‑ Collect average kurtosis value after 1‑hour operation of new bearing as K_NORMAL.
‑ Simulate insufficient lubrication (artificially reduce grease supply); record kurtosis at the first occurrence above 3.5 as K_WARN.
‑ Record kurtosis value when obvious bearing abnormal noise occurs as K_ALARM.
Hardware Installation
‑ Vibration sensor is fixed vertically on bearing housing by magnetic base to guarantee signal without attenuation.
‑ Edge acquisition unit connects to PLC via industrial Ethernet (Cat‑5e cable, distance ≤ 100 m).
Software Configuration
‑ Edge acquisition unit: deploy kurtosis‑calculation algorithm; configure Modbus slave address = 1.
‑ PLC: compile communication program (call Modbus TCP library) and decision‑making logic (ladder diagram); map HMI variables.
Commissioning Process
Static commissioning: Input simulated kurtosis values (2.5, 5.0, 7.0) manually and verify whether PLC outputs match expected logic.
Dynamic commissioning: Start equipment for continuous 24‑hour operation; record kurtosis variation curve and optimize thresholds.
Linkage test: Trigger “lubrication‑required” status; verify lubrication‑pump action and HMI alarm performance.
‑ Real‑time performance: Local processing by edge computing; latency ≤ 200 ms from signal acquisition to kurtosis output.
‑ Accuracy: Kurtosis is sensitive to early‑stage insufficient lubrication; problems can be detected 3‑7 days earlier than manual inspection.
‑ Automation: PLC triggers lubrication pump automatically, reduces manual intervention and avoids insufficient or excessive lubrication.
‑ Scalability: Edge acquisition unit allows connection of temperature sensors for auxiliary bearing‑condition judgment; data can be uploaded to cloud platforms for remote monitoring.
Note: In practical application, thresholds and sampling parameters shall be adjusted according to equipment and bearing parameters. It is recommended to compare with manual‑inspection results in initial phase for iterative optimization of decision‑making logic.